Customization: | Available |
---|---|
Application: | Submersible Pump Cable |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of US$ 0.01/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specifications:
Insulation:
POLYVINYL CHLORIDE & NYLON
Jacket:
POLYVINYL CHLORIDE
Sizes:
14 - 500 MCM, 90°C Dry, 75°C Wet
Applications:
Heavy duty (double jacketed), Flat Submersible pump cable suitable for use within well casings for wiring deep well fresh or salt water submersible pumps.
Conductor:
Class C, soft drawn, bare copper per ASTM B3 and ASTM B8.
Insulation:
Heat and moisture resistant, polyvinyl chloride meeting the requirements of UL 83 for Type THHN and THWN wires. The insulation is acceptable for use in locations at 90?C dry or 75?C wet. The insulation thickness is in accordance with UL 83.
Conductor Jacket:
A nylon jacket is applied directly to the surface of the PVC insulation. Nylon shall meet the requirements of UL 83. The thickness is in accordance with UL 83.
Ground Conductor:
Class C, soft drawn bare copper per per ASTM B3 and ASTM B8. The conductor is insulated with PVC/Nylon and the nominal overall diameter shall equal the insulated circuit conductors
Meets the requirement of UL - 83 IEC 60245, DIN VDE 0282 PART 810, BS 6007 & BS 6899
600 volts, 90° C Dry & Wet
Designed for heavy duty use
Temperature range -40° to 90°
ROHS compliance (lead free)
Flat submersible 600 V pump cable suitable for use within deep well fresh or salt water submersible pumps.
Contraction - Rubber AWG Pump Cables
Class C Flexible, bare copper
Insulation : PVC or Rubber
Sheath : PVC or Rubber
Colour Code : Black - Yellow - Red (Without Ground)
Black - Yellow - Red - Green (With Ground)
Flat Jacketed Submersible Pump Cables Without Ground | |||||
CONDUCTOR SIZE (AWG) | NO OF CONDUCTOR | NOS OF DIA. OF WIRE | CORE DIA. (MM) | NOMINAL SHEATH THICKNESS (MM) | CABLE DIA. |
14 | 3 | 41 x 0.254 | 3.85 | 1.15 | 14.60 x 6.40 |
12 | 3 | 65 x 0.254 | 4.50 | 1.15 | 16.80 x 7.40 |
10 | 3 | 105 x 0.254 | 5.30 | 1.15 | 18.70 x 7.90 |
8 | 3 | 168 x 0.254 | 6.50 | 1.40 | 23.70 x 9.90 |
6 | 3 | 226 x 0.254 | 8.00 | 1.40 |
28.00 x11.40 |
4 | 3 | 420 x 0.254 | 10.10 | 2.00 | 35.50 x14.70 |
2 | 3 | 665 x 0.254 | 11.30 | 2.00 | 39.50 x16.20 |
1 | 3 | 817 x 0.254 | 13.60 | 2.20 | 45.50 x18.30 |
1/0 | 3 | 1045 x 0.254 | 13.60 | 2.20 | 45.50 x18.30 |
2/0 | 3 | 1330 x 0.254 | 16.60 | 2.20 | 51.00 x20.00 |
3/0 | 3 | 1672 x 0.254 | 18.00 | 2.40 | 60.00 x23.50 |
4/0 | 3 | 2116 x 0.254 | 19.80 | 2.65 | 65.00 x25.00 |
Flat Jacketed Submersible Pump Cables WITH Ground | ||||||
CONDUCTOR SIZE (AWG) | NO OF CONDUCTOR | Nos & Dia. of Wire | Ground Conductor Size (AWG) | CORE DIA. (MM) | NOMINAL SHEATH THICKNESS (MM) | CABLE DIA. (MM) |
14 | 3 | 41 X 0.254 | 14 | 3.85 | 1.15 | 18.00 x6.50 |
12 | 3 | 65 X 0.254 | 12 | 4.50 | 1.15 | 21.00 x7.60 |
10 | 3 | 105 X 0.254 | 10 | 5.30 | 1.15 | 24.30 x7.90 |
8 | 3 | 168 X 0.254 | 10 | 6.50 | 1.40 | 29.70 x9.90 |
6 | 3 | 266 X 0.254 | 8 | 8.00 | 2.00 | 36.00 x11.80 |
4 | 3 | 420 X 0.254 | 8 | 10.10 | 2.00 | 45.10 x14.70 |
2 | 3 | 665 X 0.254 | 6 | 11.30 | 2.20 | 50.10 x16.20 |
1 | 3 | 817 X 0.254 | 6 | 13.60 | 2.20 | 58.10 x19.00 |
1/0 | 3 | 1045 X 0.254 | 6 | 15.60 | 2.20 | 58.10 x19.00 |
2/0 | 3 | 1330 X 0.254 | 6 | 18.00 | 2.20 | 66.50 x21.50 |
Note :
The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
In view of continuous improvements in our design and process, specifications given here in are subject change without notice.
ADVANTAGES
Cut, tear and abrasion resistant
Exceptional long term performance
Excellent resistance to oils, acids, chemicals and ozone
Excellent impact and weather resistance
Excellent electrical propertise