Bare Copper Conductor PE XLPE Insulated aluminium mylar tape Screen Galvanized steel wire Armoured Instrument Cable
Application
For transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group
ΙΙ classified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public
mains electricity supply.
Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.
1. Conductor: Plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5 mm² flexible, 0.75 mm² flexible or 1.5mm²
stranded
2. Insulation: Polyethylene PE
Colour code: black / blue;
with numbered tape under separator tape of the pair screen
3. Pair screen: 24 µm aluminium / PETP tape over tinned copper drain wire, 0.5 mm²
4. Collective screen: 24 µm aluminium / PETP tape over tinned copper drain wire, 0.5 mm²
5. Bedding: polyethylene PE, black
6. Armour: galvanized round steel wires
7. Outer sheath: Polyvinyl chloride PVC, black
*Flame retardant
*Oil resistant,
*Anti-rodent&termite
These properties could be offered upon requested.
Technical Data
Temperature range:
-40°C up to +70°C (during operation)
- 5°C up to +50°C (during installation)
Min. bending radius:
8 x cable-Ø