Application of xlpe abc cable
Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead powerdistribution as compared to the conventional bare conductor overhead distribution system.
It provides higher level of safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost.
LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for
temporary service at construction sites, as a service drop (power pole to service entrance),as a secondary cable (pole to pole) or street lighting.
This over-head cable providesreinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140.
It is not flame retardant. But this could be if requested change to a flame retardant cable.
Standard of xlpe abc cable
Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/
NZS 3560-1 standards
Construction of xlpe abc cable
Conductor: Aluminium conductor, round stranded compressed (RM).
insulation: XPLE compound, UV-resistant.
Core identification: 1, 2 resp. 3 raised longitudinal ribs on the surface of the cores.
The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm²
and a minimum of 16 ribs for cores above 50 mm². In the case of five core bundles the
surface of the protective core should be smooth.
Electrical Properties | |
rated Voltage0.6/1kV | |
Test Voltage | 4 Veff kV |
minimum laying Temperature | -20°C |
operating Temperature | -40°C~ +90°C |
maximum Short-circuit Temperature | 250°C |
maximum Conductor Temperature | 80°C |
minimum Bending radius | 18×OD |
Construction Parameters of xlpe abc cable
TNB Specification (IEC 60502)
number of cores xNominal cross Section | overall diameter | weight | Maxinum conductor Resistance | Minimun breaking Load | current Rating |
No.xmm2 | mm | kg/km | Ω/Km | KN | A |
1x16+1x25 RM | 15.3 | 160 | 1,910 | 2,5 | 72 |
3x16+1x25 RM | 19 | 290 | 1,200 | 4,0 | 107 |
3x25+1x25 RM | 23.2 | 400 | 0,868 | 5,5 | 132 |
3x35+1x25 RM | 25.6 | 500 | 0,641 | 8,0 | 165 |
3x50+1x35 RM | 30 | 680 | 0,443 | 10,7 | 205 |
3x70+1x50 RM | 34.9 | 920 | 0,320 | 13,7 | 240 |
3x95+1x70 RM | 40.6 | 1270 | 0,253 | 18,6 | 290 |
3x120+1x70 RM | 44.1 | 1510 | 0,206 | 23,2 | 334 |
3x150+1x95 RM | 49.2 | 1870 | 0,164 | 28,7 | 389 |
3x185+1x120 RM | 54.9 | 2340 | 0,125 | 37,2 | 467 |
3x25+1x25+1x16 RM | 23.2 | 470 | 1,910 | 2,5 | 72 |
3x35+1x25+1x16 RM | 25.6 | 560 | 1,200 | 4,0 | 107 |
3x50+1x35+1x16 RM | 30 | 740 | 0,868 | 5,5 | 132 |
3x70+1x50+1x16 RM | 34.9 | 980 | 0,641 | 8,0 | 165 |
3x95+1x70+1x16 RM | 40.6 | 1330 | 0,443 | 10,7 | 205 |
3x120+1x70+1x16 RM | 44.1 | 1580 | 0,320 | 13,7 | 240 |
3x150+1x95+1x16 RM | 49.2 | 1940 | 0,206 | 23,2 | 334 |
3x185+1x120+1x16 RM | 54.9 | 2410 | 1,910 | 2,5 | 72 |
othercross-sectionscanbeoffereduponrequest. |