Customization: | Available |
---|---|
Application: | Overhead |
Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
i) | General | ||
a) | Types of service main cable | - | As per Clause 1.0 |
b) | Nominal cross section area | - | 10mm2 & 16mm2 |
c) | NO. of cable& nominal dia. | - | 7/1.35mm (10 mm2) |
7/1.70mm (16 mm2) | |||
d) | Number of cores | - | 2x for single phase and 4x for three phase c/w 2x1.13 mm2 pilot cores |
e) | Colour of sheath | - | Black |
ii) | Conductor | ||
a) | Conductor material | - | Aluminum (EC Grade) |
b) | Conductor Diameter | - | 5.10 mm for 16mm2 |
4.05 mm for 10mm2 | |||
c) | Conductor Resistance at 20 ºC | - | 16mm2 <1.15 ohm/km |
10mm2<1.83 ohm/km | |||
d) | Tensile Strength | - | 125 - 165 N/mm |
e) | Pilot cores for communication | ||
Conductor material | Copper | ||
Diameter mm | 1.13 mm2 | ||
Number | 2 | ||
f) | Wrapping Test | No crack | |
iii) |
Insulation |
||
a) | Insulation Type | - | XLPE |
b) | Thickness (minimum) | - | 1 mm |
c) | Smallest measure of Thickness | - | 0.8 mm |
d) | Tensile Strength of Non aged | - | N/mm 12.5 min. |
e) | Tensile Strength of Aged | - | N/mm 12.5 min. |
f) | Elongation at break of Non aged | - | % 125 |
g) | Elongation at break of aged | - | % 125 |
h) | Heat shock test | - | Non crack |
i) | Shrinkage Test | - | % 3 |
iv) | Sheath | ||
a) | Sheath type | - | XLPE type 6 as per 7655 |
b) | Thickness | - | 1 mm |
c) | Smallest measure of Thickness | - | 0.75 mm |
d) | Tensile Strength of non aged | - | 6N/mm |
e) | Tensile Strength of aged | - | 6N/mm |
f) | Elongation at break of non aged | - | 125 % |
g) | Elongation at break of aged | - | 125% |
h) | Heat shock test | - | No crack |
v) | Test on Unsheathed Cable | ||
a) | Spark test | - | 10kV |