Customization: | Available |
---|---|
Application: | Construction, Underground, Industrial |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specification | Conductor structure | Conductor diameter (mm) |
Conductor package with specifications (mm) |
Insulation thickness (mm) |
Taping Specifications (mm) |
Sheath thickness (mm) |
Reference outer diameter (mm) |
Reference Weight (kg/km) |
1×1.5 | 30/0.25 | 1.56 | 8×0.05 | 0.8 | 1.4 | 6.1 | 55.6 | |
1×2.5 | 49/0.25 | 2.00 | 8×0.05 | 0.9 | 1.4 | 6.8 | 72.4 | |
1×4 | 56/0.30 | 2.56 | 8×0.05 | 1.0 | 1.5 | 7.7 | 99.8 | |
1×6 | 84/0.30 | 3.54 | 10×0.05 | 1.0 | 1.6 | 8.4 | 128.1 | |
1×10 | 77/0.40 | 4.56 | 10×0.20 | 1.2 | 1.8 | 11.2 | 206.6 | |
1×16 | 7×18/0.40 | 5.50 | 15×0.20 | 1.2 | 1.9 | 12.3 | 282.4 | |
1×25 | 7×28/0.40 | 7.10 | 15×0.20 | 1.4 | 2.0 | 14.5 | 407.0 | |
1×35 | 7×38/0.40 | 8.20 | 20×0.20 | 1.4 | 2.2 | 16.0 | 521.3 | |
1×50 | 19×20/0.40 | 9.80 | 25×0.20 | 1.6 | 2.4 | 18.4 | 714.59 | |
1×70 | 18×20/0.50 | 11.50 | 30×0.20 | 1.6 | 2.6 | 20.5 | 976.94 | |
1×95 | 19×24/0.50 | 13.40 | 30×0.20 | 1.8 | 2.8 | 23.2 | 1231.49 | |
1×120 | 19×30/0.50 | 14.60 | 30×0.20 | 1.8 | 3.0 | 24.8 | 1554.5 | |
1×150 | 19×38/0.50 | 16.30 | 30×0.20 | 2.0 | 3.2 | 27.3 | 1882.0 | |
1×185 | 37×24/0.50 | 18.50 | 30×0.20 | 2.2 | 3.4 | 30.3 | 2259.9 | |
1×240 | 60×20/0.50 | 21.30 | 30×0.20 | 2.4 | 3.5 | 33.7 | 2941.0 | |
1×300 | 61×24/0.50 | 24.10 | 30×0.20 | 2.6 | 3.6 | 37.1 | 3545.4 | |
1×400 | 61×32/0.50 | 25.50 | 30×0.20 | 2.8 | 3.8 | 39.3 | 4532.9 | |
2×1.5 | 30/0.25 | 1.56 | 8×0.05 | 0.8 | 1.5 | 9.6 | 133.5 | |
2×2.5 | 49/0.25 | 2.00 | 8×0.05 | 0.9 | 1.7 | 11.4 | 191.9 | |
2×4 | 56/0.30 | 2.56 | 8×0.05 | 1.0 | 20×0.20 | 1.8 | 13.6 | 286.9 |
2×6 | 84/0.30 | 3.54 | 8×0.05 | 1.0 | 20×0.20 | 2.0 | 15.0 | 429.6 |
2×10 | 77/0.40 | 4.56 | 10×0.20 | 1.2 | 30×0.20 | 3.1 | 22.0 | 848.7 |
2×16 | 7×18/0.40 | 5.50 | 15×0.20 | 1.2 | 30×0.20 | 3.3 | 24.2 | 1097.8 |
2×25 | 7×28/0.40 | 7.10 | 15×0.20 | 1.4 | 40×0.20 | 3.6 | 28.8 | 1596.4 |
2×35 | 7×38/0.40 | 8.20 | 20×0.20 | 1.4 | 40×0.20 | 3.9 | 31.6 | 1980.8 |
2×50 | 19×20/0.40 | 9.80 | 25×0.20 | 1.6 | 40×0.20 | 4.3 | 36.4 | 2690.3 |
2×70 | 18×20/0.50 | 11.50 | 30×0.20 | 1.6 | 40×0.20 | 4.6 | 40.4 | 3512.9 |
2×95 | 19×24/0.50 | 13.40 | 30×0.20 | 1.8 | 40×0.20 | 5.0 | 45.8 | 4490.6 |
3×1.5 | 30/0.25 | 1.56 | 8×0.05 | 0.8 | 1.6 | 10.3 | 159.8 | |
3×2.5 | 49/0.25 | 2.00 | 8×0.05 | 0.9 | 1.8 | 12.2 | 230.0 |
Items | Description |
Rated Voltage |
Rated voltage 0.45/0.75kV, using the AC system should not be more than 0.9kV. |
Operating Temperature | The long-term maxmium operating temperature of cable conductor is 65 ºC. When in short circuit, the maximum temperature is no more than 160 ºC, time of duration is no more than 5 S. |
Environment Temperature | Minimum operating environment temperature is -10 ºC. |
Laying Temperature | Cable laying temperature should be not lower than 0 ºC |
Bending Radius | Recommended minimum bending radius: no more than 10D. |
Storage | Finished cable should be stored at -10~35 ºC, humidity is below 80% of the environment, and avoid direct sunlight and the rain, keep ventilation and dry environment. Keep away from acids, alkalis, mineral oils etc.. According to the above requirements for storage and use, the cable can be used for more than 2 years long. |
Installation Instruction | When installed, the environment temperature should not be lower than -10 ºC. if the environment temperature is lower 0 ºC, the cable should be preheated before installation. To avoid the machnical damage of the internal cable, the bending radius of multi-cores cable is not more than10D. ("D "means the out diameter of cable) |