Customization: | Available |
---|---|
Application: | Construction, Underground |
Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. Application and Main type
Type |
Description |
Main Application |
|
Copper Conductor |
Aluminum Conductor |
||
YJV Cu/XLPE/PVC |
YJLV Al/XLPE/PVC |
Copper or aluminum conductor XLPE insulated, Copper tape screen PVC sheathed power cable |
For laying indoor, tunnel, underground and cannel. Unable to bear external mechanical pulling force and pressure during laid. |
YJV Cu/XLPE/L(H)DPE |
YJLV Al/XLPE/L(H)DPE |
Copper or aluminum conductor XLPE insulated, Copper tape screen PE/LDPE/HDPE sheathed power cable |
|
YJE Cu/XLPE/LSOH |
YJLE Al/XLPE/LSOH |
Copper or aluminum conductor XLPE insulated, Copper tape screen LSOH sheathed power cable |
|
YJSV Cu/XLPE/CWS/PVC N2XS(SE)Y |
YJLSV Al/XLPE/CWS/PVC N2XS(SE)Y |
Copper or aluminum conductor XLPE insulated, Copper wire+ Copper tape screen PVC sheathed power cable |
For laying indoor, tunnel, underground and cannel. Unable to bear external mechanical pulling force and pressure during laid, fault current requires large. CWS(Copper wire screen) type: A: Fixed section B: Full/one third/one sixth/one eighth/one sixteenth neutral |
YJSY Cu/XLPE/CWS/L(M.H)DPE N2XS(SE)2Y |
YJLSY Al/XLPE/CWS/L(M.H)DPE N2XS(SE)2Y |
Copper or aluminum conductor XLPE insulated, Copper wire+ Copper tape screen PE/LDPE/HDPE sheathed power cable |
|
YJE Cu/XLPE/CWS/LSOH |
YJLE Al/XLPE/CWS/LSOH |
Copper or aluminum conductor XLPE Copper wire+ Copper tape screen LSOH sheathed power cable |
|
YJV22 Cu/XLPE/STA/PVC |
YJLV22 Al/XLPE/STA/PVC |
Copper or aluminum conductor XLPE insulated, Copper tape screen, steel tape armored, PVC sheathed power cable |
For laying indoor, tunnel, underground and cannel. Able to bear external mechanical forces, but unable to bear large pulling force. |
YJV23 Cu/XLPE/STA/L(M.H)PE |
YJLV23 Al/XLPE/STA/L(M.H)PE |
Copper or aluminum conductor XLPE insulated, Copper tape screen, steel tape armored, PE/LDPE/HDPE sheathed power cable |
|
WD-YJY23 Cu/XLPE/STA/LSOH |
WD-YJLY23 Al/XLPE/STA/LSOH |
Copper or aluminum conductor XLPE insulated, Copper tape screen, steel tape armored, PVC sheathed power cable
|
|
YJSV22 Cu/XLPE/CWS/STA/PVC N2XSEBY |
YJLSV22 Al/XLPE/CWS/STA/PVC N2XSEBY |
Copper or aluminum conductor XLPE insulated, Copper wire+ Copper tape screen, steel tape armored, PVC sheathed power cable |
For laying indoor, tunnel, underground and cannel. Able to bear external mechanical forces, but unable to bear large pulling force. fault current requires large. CWS(Copper wire screen) type: A: Fixed section |
2. Scope of voltage grade and core number and cross-section
a) National standard
Rated voltage(KV) |
3.6/6 |
6/6 |
6/10 |
8.7/10 |
8.7/15 |
12/15 |
12/20 |
18/20 |
18/30 |
21/35 |
26/35 |
|
Core Number |
1 core, 3 core |
|||||||||||
Cross-section mm2 |
1C |
25~800 |
35~800 |
|||||||||
3C |
25~400 |
35~400 |
b) IEC/BS/DIN standard
Rated voltage(KV) |
3.6/6 |
6/6 |
6/10 |
8.7/10 |
8.7/15 |
12/15 |
12/20 |
18/20 |
18/30 |
21/35 |
26/35 |
|
Core Number |
1 core, 3 core |
|||||||||||
Cross-section mm2 |
1C |
25~800 |
35~800 |
|||||||||
3C |
25~400 |
35~400 |
c) ASTM standard
Rated voltage(KV) |
5001-8000 |
8001-15000 |
15001-25000 |
25001-28000 |
28001-35000 |
35001-46000 |
|
1 core, 3 core |
|||||||
Cross-section mm2 |
1C |
6AWG~1600kcmil |
2AWG~1600kcmil |
1AWG~1600kcmil |
2AWG~1600kcmil |
1/0AWG~1600kcmil |
|
3C |
6AWG~1600kcmil |
2AWG~1600kcmil |
1AWG~1600kcmil |
2AWG~1600kcmil |
4/0AWG~1600kcmil |
3. Service conditions and operation parameters of cable
A) Max. conductor operating temperature: 90oC
B) Short circuit temperature: 250oC
C) Ambient temperature: 30oC
D) Soil temperature: 20oC
E) Depth of laying in direct: 0.8m
F) Thermal resistance of soil: 150oC.cm/W
G) Thermal resistance of ducts: 120oC.cm/W
Our Main Product: