Customization: | Available |
---|---|
Application: | Construction, Underground, Industrial, Power Station |
Voltage: | High Voltage Cable |
Still deciding? Get samples of US$ 51.775/Meter
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
11KV 3x185mm2,Cu/XLPE/CTS/PVC/SWA/PVC CABLE
Technical Data Sheet | |||
11KV 3x185mm2,Cu/XLPE/CTS/PVC/SWA/PVC CABLE | |||
ITEM | DESCRIPTION | UNIT | Data |
Rated Voltage | KV | 11 | |
1 | Reference standard | -- | IEC60502-2 |
2 | Conductor | ||
Material | -- | Stranded Copper Wire, Compacted round |
|
Core number x size | -- | 3x185mm2 | |
Stranding no.of wire | no. | 37 | |
Approx. Conductor Diameter | mm | 16.2 | |
Max. D.C. Resistance of conductor | Ω/km | 0.0991 | |
3 | Conductor Screen | ||
Material | Semi-conducting compound | ||
Nominal thickness | mm | 0.6 | |
4 | Insulation | ||
Material | -- | XLPE | |
Nominal thickness | mm | 3.4 | |
5 | Insulation screen | ||
Material | -- | Semi-conducting compound | |
Nominal thickness | mm | 0.7 | |
6 | Metal shield layer | ||
Material | -- | Copper tape | |
Copper tape thickness | mm | Min.0.06 | |
7 | Inner sheath | ||
Material | -- | PVC | |
Nominal Thickness | mm | 1.7 | |
8 | Armour layer | ||
Material of armour | -- | Steel wire | |
Single wire dia. | mm | Min.1.6 | |
9 | Outer sheath | ||
Material | -- | PVC | |
Nominal thickness | mm | 3.2 | |
10 | Complete cable | ||
Overall diameter (approx.) | mm | 72 | |
Weight per km (approx.) | Kg/km | 10938 |