• 2X10mm2 Service Cable Aluminum Conductor

2X10mm2 Service Cable Aluminum Conductor

Type: Insulated
Conductor Type: Stranded
Application: Overhead
Conductor Material: Copper
Sheath Material: PVC or PE
Insulation Material: XLPE
Customization:

360° Virtual Tour

Diamond Member Since 2009

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
SAC
Material Shape
Round Wire
Range of Application
Service Entrance
Certification
ISO9001, CE, CCC
Brand
Yifang
Sheath Color
Black
Transport Package
Drum, Reel or According to Customers′ Request
Specification
drum
Trademark
Yifang
Origin
China
HS Code
8544492100
Production Capacity
50, 000km Per Month

Product Description


2X10mm2 Service Cable Aluminum Conductor
Aerial Concentric Service Cable with Communication Cable 

ne phase phase concentric cores Service Drop aerial Cables
Structure
Wires of Phase Conductor
Wires of Neutral Conductor 
Factory Test Report
 
Pilot Communication pair of Cores 
2X10mm2 Service Cable Aluminum Conductor
 
4.2.2.1 Typical construction Material Circular stranded plain annealed Aluminum conductors (Class 2) as specified in KS 04-1022 and shall comply with all provisions of KS 04-187, Left-hand direction of lay
Direction of lay
4.2.2.2 Insulation As per KS 04-1022, KS 04-188 and BS 6746 PVC compound - type TI 1 as specified in KS 04-1022, KS 04-188 and BS 6746
4.2.2.3 Min Thickness of insulation As per KS 04-1022 1.55mm
4.2.3 Concentric layer
4.2.3.1 Neutral-earth conductor(Material & construction)
  Material Plain anneal aluminum Plain annealed Aluminum wires in accordance with KS 04-1022 and as required by clause 4 of BS 7870-3.20:2001
Cover material Polymeric compound
Properties of cover material Tensile strength 4 N/mm2 Comply
Elongation,% 50 Comply
4.2.3.2 Communication cable
4.2.3.2.1 Construction
The communication cable is a two (2)-core single equipment cables helically wrapped over the core cable adjacent to the earth-neutral conductors. The wires shall be stranded (class 2 of BS 6360:1991), which may be screened, for purposes of internal wiring of electronic and other equipment according to BS 4808-1:1972.
4.2.3.2.1.2 Material As per BS 6360 and BS 2011, Test 2T, Method 1 Standard annealed Copper, smoothly drawn, uniform in quality, free from defects and uniformly coated with pure tin satisfying the mechanical requirements of BS 6360 and all conductors shall meet the test for soldering given in BS 2011, Test 2T - Method 1
4.2.3.2.1.3   Length of lay Not exceed 20 times(146.5mm) the calculated diameter over the assembled conductor. The direction of lay of the strands is Right-hand
Direction of lay of the strand
4.2.3.2.1.4 Joints Shall be essentially smooth, and shall not have any sharp projections No joint
4.2.3.2.1.5 Colours Correspond with standard colours shown in IEC 60304:1982 White & Blue
4.2.3.2.2 Insulation
  Material PVC compound - type TI 1as specified in KS 04-1022, KS 04-188 and BS 6746 PVC compound - type TI 1 as specified in KS 04-1022, KS 04-188 and BS 6746
Dimensions As per table 2 Min.1.55mm
4.2.3.3 Non hygroscopic string separation Shall be approximately the same as the diameter on the individual insulated communication cables. Conformity shall be checked through visual examination as per BS7870-3.20:2001 clause 14.3
4.2.3.4 Application of concentric layer
  Lay direction Right  hand lay Right hand lay
Composition Neutral &earth conductor
and communication cable
Neutral &earth conductor
and communication cable
Application Applied together with string separation  Either one or two string hygroscopic string separation shall be located on either side of the group of neutral-earth continuity conductor to separate them from the group of insulated communication cables
Coverage 90% 90%
4.2.3.5 Binders Synthetic binders tape Overlapped Synthetic binders tape as per BS BS7870-3.20:2001 Clause 7
4.2.4 Over-sheath or outer Jacket
4.2.4.1 Material As per KS 04-1022 and
BS 6746
Extruded layer of Black PVC compound - type TM 1 as specified in KS 04-1022 and BS 6746
In accordance with KS 04-1022
Oversheath testing In accordance with
KS 04-1022
4.2.4.2 Minimum thickness Shall not fall below the values on Table 2 by>(15% + 0.1mm).  Min1.09
4.2.4.3 Non-metallic rip-cord Shall be laid under the sheath Laid under the sheath, incorporate the
manufacturer's identification colours.
Shall incorporate the manufacturer's identification colour
4.3 Standard sizes and characteristics As per table 2, Table 3 and as per the requirement of clause 4 of BS 7870-3.20:2001. comply with Table 2 and as
per the requirement
Of clause 4 of BS7870-3.20:2001

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2009

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
122
Year of Establishment
2001-02-22