Application: | Construction, Underground, Industrial, Power Station |
---|---|
Voltage: | Low and Medium Voltage Cable |
Current: | DC & AC |
Insulation Material: | XLPE/PVC/PE |
Certification: | ISO, CCC, CE, RoHS, UL, VDE |
Conductor Material: | Cu or Al |
Customization: |
---|
Suppliers with verified business licenses
Class 2 stranded conductors for single-core and multi-core cables | |||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
Nominal crosssectional area | Minimum number of wires in the conductor | Maximum resistance of conductor at 20ºC | |||||||
Circular | Circular compacted | Shaped | Annealed copper conductor | Aluminium or aluminium alloy conductor | |||||
Cu | Al | Cu | Al | Cu | Al | Plain wires | Metal-coated wires | ||
mm2 | Ω/KM | Ω/KM | Ω/KM | ||||||
0.5 | 7 | 36 | 36.7 | ||||||
0.75 | 7 | 24.5 | 24.8 | ||||||
1 | 7 | 18.1 | 18.2 | ||||||
1.5 | 7 | 6 | 12.1 | 12.2 | |||||
2.5 | 7 | 6 | 7.41 | 7.58 | |||||
4 | 7 | 6 | 4.61 | 4.7 | |||||
6 | 7 | 6 | 3.08 | 3.11 | |||||
10 | 7 | 7 | 6 | 6 | 1.83 | 1.84 | 3.08 | ||
16 | 7 | 7 | 6 | 6 | 1.15 | 1.16 | 1.91 | ||
25 | 7 | 7 | 6 | 6 | 6 | 6 | 0.727 | 0.734 | 1.2 |
35 | 7 | 7 | 6 | 6 | 6 | 6 | 0.524 | 0.529 | 0.868 |
50 | 19 | 19 | 6 | 6 | 6 | 6 | 0.387 | 0.391 | 0.641 |
70 | 19 | 19 | 12 | 12 | 12 | 12 | 0.268 | 0.27 | 0.443 |
95 | 19 | 19 | 15 | 15 | 15 | 15 | 0.193 | 0.195 | 0.32 |
120 | 37 | 37 | 18 | 15 | 18 | 15 | 0.153 | 0.154 | 0.253 |
150 | 37 | 37 | 18 | 15 | 18 | 15 | 0.124 | 0.126 | 0.206 |
185 | 37 | 37 | 30 | 30 | 30 | 30 | 0.0991 | 0.1 | 0.164 |
240 | 37 | 37 | 34 | 30 | 34 | 30 | 0.0754 | 0.0762 | 0.125 |
300 | 61 | 61 | 34 | 30 | 34 | 30 | 0.0601 | 0.0607 | 0.1 |
400 | 61 | 61 | 53 | 53 | 53 | 53 | 0.047 | 0.0475 | 0.0778 |
500 | 61 | 61 | 53 | 53 | 53 | 53 | 0.0368 | 0.0369 | 0.0605 |
630 | 91 | 91 | 53 | 53 | 53 | 53 | 0.0283 | 0.0286 | 0.0469 |
800 | 91 | 91 | 53 | 53 | 0.0221 | 0.0224 | 0.0367 | ||
1000 | 91 | 91 | 53 | 53 | 0.0176 | 0.0177 | 0.0291 | ||
1200 | b | 0.0151 | 0.0151 | 0.0247 | |||||
1400a | 0.0129 | 0.0129 | 0.0212 | ||||||
1600 | 0.0113 | 0.0113 | 0.0186 | ||||||
1800a | 0.0101 | 0.0101 | 0.0165 | ||||||
2000 | 0.009 | 0.009 | 0.0149 | ||||||
2500 | 0.0072 | 0.0072 | 0.0127 | ||||||
a.These sizes are non-preferred. Other non-preferred sizes are recognized for some specialized applications but are not within the scope of this standard. b.The minimum number of wires for these sizes is not specified. These sizes may be constructed from 4, 5 or 6 equal segments (Milliken). c.For stranded aluminium alloy conductors having the same nominal cross-sectional area as an aluminium conductor the resistance value should be agreed between the manufacturer and the purchaser. |
|||||||||