Customization: | Available |
---|---|
Application: | Construction, Underground, Industrial, Power Station |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of US$ 0.01/Meter
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
0.6/1kv U 1000 ARVFV Cable (HGE) 3X240+95mm2
CONSTITUTION
TECHNICAL DATA SHEET | |||
Câble ARVFV(HGE) 3x240mm²+95mm² Alu | |||
Item | Description | Unit | Data |
1 | Standard | IEC 60502-1 | |
2 | Size | 3x240+95mm2 | |
3 | Rated Voltage | kV | 0.6/1 |
4 | Phase core | ||
Cores | 3 | ||
Norminal Cross Sectional Area | mm2 | 240 | |
Conductor | Compact sector aluminum | ||
Standing No.Of Wire | no.s | Min.30 | |
Max.DC Resistance at 20ºC | Ω/km | 0.125 | |
Insulation | XLPE | ||
Norminal Thickness | mm | 1.7 | |
5 | Earth core | ||
Cores | 1 | ||
Norminal Cross Sectional Area | mm2 | 95 | |
Conductor | Compact sector aluminum | ||
Standing No.Of Wire | no.s | Min.15 | |
Max.DC Resistance at 20ºC | Ω/km | 0.32 | |
Insulation | XLPE | ||
Norminal Thickness | mm | 1.1 | |
6 | Filler(if any) | PP | |
7 | Wrapping tape | Non-woven clothing tape | |
8 | Inner Sheath | PVC | |
Norminal Thickness | mm | 1.6 | |
9 | Armor | Steel tape | |
Norminal Thickness | 0.5 | ||
10 | Outer Sheath | PVC | |
Norminal Thickness | mm | 2.8 | |
11 | Overall diameter | mm | 57.8 |
12 | Approx.Weight | kg/km | 4765 |