XLPE/PVC Insulation LV (Low Voltage) Power Cable
1.XLPE/PVC Insulation LV (Low Voltage) Power Cable cable belongs to cables rated voltage up to 1KV. They are used for laying indoor, tunnel, underground, canal, water and seabed, etc .
Standard available such as ASTM , BS , DIN ,NFC , AS/NZS , CSA , IS , etc.
2.Brief Construction:
2.1 Number of Core : 1Core , 2Core,3Core , 4Core , 5Core , 3+1Core(3.5Core) , 3+2 Core , 4+1Core , etc.
2.2 Conductor material: Copper or Aluminum (Stranded Round /Stranded compacted round/stranded compacted sector)
2.3 Insulation Material: XLPE/PVC/PE/LSHF
2.4 Inner sheath (applicable if there is armour layer): PVC/PE
2.5 Armour layer (if required) :Galvanized steel wire / Steel Tape
2.6 Outer sheath : PVC/PE
3.The max. conductor long time permissible operating temperature is 70 degree for PVC Insulation and 90degreefor XLPE Insulation ; In short circuit, max. Temperature is 160 degree for PVC Sheath and 250degreefor PVC Sheath.
4.Packing : In roll / In wooden drum / In Iron-wooden drum / In steel drum.
5.Certificate: ISO , CE , SGS, SONCAP , BV , COC,ETC.
6.For other detailed information, pls contact us directly .
Nominal Cross Section mm 2 |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
Cu core Ohm/km |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
0.727 |
Al core Ohm/km |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.91 |
1.2 |
Nominal Cross Section mm 2 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
Cu core Ohm/km |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.0991 |
Al core Ohm/km |
0.868 |
0.641 |
0.443 |
0.32 |
0.253 |
0.206 |
0.164 |
Nominal Cross Section mm 2 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
Cu core Ohm/km |
0.0754 |
0.06 |
0.047 |
0.0366 |
0.0283 |
0.0221 |
0.0176 |
Al core Ohm/km |
0.125 |
0.1 |
0.0778 |
0.0605 |
0.0469 |
0.0367 |
0.0291 |